Estimate the length of radiant floor tubing and the number of loops for a room. Enter the floor area, the tube spacing and the longest loop you want.
Radiant Heat Layout Calculator
Radiant floor heating tubing length and loop count for a room, from floor area and tube spacing.
Starting values: 200 ft² of floor, tubing at 9 in spacing and loops of 300 ft at most. The calculator gives about 293 ft of tubing in 1 loop.
How the calculator lays out the tubing
Tubing length = (area ÷ spacing) × 1.1
Loops = tubing length ÷ maximum loop length, rounded up
Where:
- Area is the floor area to heat.
- Spacing is the distance between tube runs, in the same system as the area.
- 1.1 adds 10 percent for turns and extra length.
- Maximum loop length is the longest single circuit you want on the manifold.
Dividing the area by the spacing gives the length of tube that fits at that spacing. At 9 in, or 0.75 ft, each square foot needs 1.33 ft of tube. The loop count is rounded up, because a part of a loop is still a loop. The inputs have unit selectors, so you can use inches, feet, millimetres or metres.
Worked examples
The starting example
200 ÷ 0.75 = 266.7 ft, and × 1.1 = 293.3 ft. With a 300 ft maximum, 293.3 ÷ 300 = 0.98, which rounds up to 1 loop.
A shorter maximum loop
A guide gives about 250 ft as the practical limit for 1/2 in tubing, because longer loops lose flow and heat output. Setting the maximum to 250 ft, the same room needs 293.3 ÷ 250 = 1.17, which rounds up to 2 loops. Each loop would then be about 146.7 ft if the tubing is split evenly.
A larger room with wider spacing
A room of 400 ft² at 12 in spacing needs 400 ÷ 1 = 400 ft, and × 1.1 = 440 ft. With a 300 ft maximum, that is 1.47 loops, so 2 loops.
The same room with tight spacing
At 6 in spacing, the 400 ft² room needs 400 ÷ 0.5 = 800 ft, and × 1.1 = 880 ft. With a 300 ft maximum, that is 2.93, so 3 loops. At 250 ft it is 3.52, so 4 loops. Halving the spacing doubles the tubing.
Choosing the tube spacing
A tubing design guide gives a standard spacing of about 8 in, and tighter spacing, down to roughly 4 in, for areas with high heat loss or floors that conduct heat poorly. Wider spacing uses less tube, but the floor surface is less even. A common approach is to space the tubing closer along exterior walls, windows and doors and wider in the middle of the room. The calculator uses one spacing for the whole area, so for a mixed layout, calculate each zone on its own and add the results.
Loop length
The same guide says longer loops cut the flow and the heat output, and cause a larger temperature drop from the start of the loop to the end. It gives about 250 ft as the practical limit for 1/2 in tubing and about 700 ft for 1 in tubing. The calculator default of 300 ft is a starting value, so set the maximum to the limit for your tube size and your system design.
What the layout leaves out
- The run from the manifold to the room is not a separate input. Add the supply and return length for each loop by hand.
- The manifold should be as close to its loops as possible and easy to reach for service. A large area may need more than one manifold.
- The calculator does not size the heat output, the boiler or the pump, and it does not include the floor construction.
For the cost of the system, see the radiant floor heating cost calculator. For other heating tools, see the unit heater sizing calculator.
Planning the layout step by step
- Measure the floor area that will be heated, leaving out areas under cabinets and fixed furniture where heat will not reach the room.
- Choose the tube spacing, using closer spacing for rooms with high heat loss.
- Enter the maximum loop length for your tube size.
- Read the tubing length and the loop count, and add the supply and return run for each loop.
- Split the area into zones if the spacing changes, and calculate each zone on its own.
Equal loops
The calculator gives the number of loops but not the length of each. If you divide the total evenly, the loop length is the total tubing divided by the loop count. For 880 ft in 3 loops, that is about 293 ft each, which is under a 300 ft limit. Splitting the tubing evenly keeps each loop within the limit.
Warm areas first
The guide suggests sending the warmest part of a loop toward the windows, doors and exterior walls, where the heat loss is highest, using a serpentine pattern, or spacing the tubing more closely there. Plan the order of the loops with this in mind.
Frequently asked questions
How much tubing do I need for radiant floor heating?
Divide the floor area by the tube spacing and add 10 percent. For 200 ft² at 9 in spacing, that is about 293 ft.
How many feet of tubing per square foot?
It is 12 divided by the spacing in inches. At 6 in spacing it is 2 ft per ft², at 9 in it is 1.33 ft, and at 12 in it is 1 ft, before the 10 percent allowance.
How long can a radiant loop be?
A tubing design guide gives about 250 ft for 1/2 in tubing and about 700 ft for 1 in tubing. Longer loops lose flow and heat output.
Does the calculator include the run to the manifold?
No. It uses the area and the spacing only, so add the supply and return length of each loop yourself.