Unit Heater Sizing Calculator: Volume & Temperature Rise

A gas or electric unit heater hangs from the ceiling or wall and heats a whole space, so its size depends on how much air it has to warm and by how many degrees. This unit heater sizing calculator multiplies the volume of the space by a rule of thumb of 0.133 BTU per hour per cubic foot per degree Fahrenheit, then by the temperature rise you want. It starts with a 40 ft by 30 ft space, a 14 ft ceiling and a 40°F rise.

Heating & Cooling Sizing Calculators

Unit Heater Sizing Calculator

BTU/h output needed from a ceiling- or wall-mounted gas or electric unit heater, from space volume and desired temperature rise.

°F
This uses a simple volume × temperature-rise rule of thumb; a real heat-loss calculation should also account for insulation, air changes and exposed walls.

How do you size a unit heater?

Multiply the length, width and ceiling height for the volume, then multiply by 0.133 and by the temperature rise. The answer is the heat output in BTU per hour that the space needs, and each variable is explained below.

Volume = Length × Width × Ceiling height
Output (BTU/h) = Volume × 0.133 × Temperature rise (°F)

The 0.133 is the calculator’s built-in rule of thumb. Its own note says it is a simple volume and temperature-rise rule and that a real heat-loss calculation should also account for insulation, air changes and exposed walls.

Worked examples

Worked example: the starting values

Volume = 40 × 30 × 14 = 16,800 ft³
Output = 16,800 × 0.133 × 40 = 89,376 BTU/h

Worked example: a small workshop

A 30 ft by 20 ft shop with a 12 ft ceiling and a 30°F rise:

Volume = 30 × 20 × 12 = 7,200 ft³
Output = 7,200 × 0.133 × 30 = 28,728 BTU/h

Worked example: a large warehouse bay

A 60 ft by 40 ft bay with a 16 ft ceiling and a 50°F rise:

Volume = 60 × 40 × 16 = 38,400 ft³
Output = 38,400 × 0.133 × 50 = 255,360 BTU/h

Worked example: a two-car garage

A 20 ft by 20 ft garage with a 10 ft ceiling and a 35°F rise:

Volume = 4,000 ft³
Output = 4,000 × 0.133 × 35 = 18,620 BTU/h

Temperature rise and output compared

For the 16,800 ft³ starting space:

Temperature rise Output
20°F 44,688 BTU/h
30°F 67,032 BTU/h
40°F 89,376 BTU/h
50°F 111,720 BTU/h

Ceiling height and output compared

For a 40 ft by 30 ft floor and a 40°F rise:

Ceiling height Volume Output
10 ft 12,000 ft³ 63,840 BTU/h
12 ft 14,400 ft³ 76,608 BTU/h
14 ft 16,800 ft³ 89,376 BTU/h
16 ft 19,200 ft³ 102,144 BTU/h

Temperature rise explained

It is the difference between the outdoor design temperature and the indoor temperature you want. If it is 20°F outside and you want 60°F inside, the rise is 40°F. Use a figure based on the coldest conditions you plan for.

Converting the result to kW

Divide BTU per hour by 3,412. The 89,376 BTU/h starting result is about 26.2 kW, which is useful when you are comparing an electric unit heater with a gas model rated in BTU per hour.

What the unit heater sizing calculator leaves out

It does not use insulation, the number of exposed walls, doors that open often, windows, ventilation or the heat from equipment and people in the space. A leaky building needs more than the formula gives, and a well-insulated one less. The radiant tube heater sizing calculator on this site uses floor area and use pattern instead, so compare the two if you are weighing different heater types.

Choosing a unit heater from the result

Compare the result with the rated output of models, not their input, since the two differ with efficiency. Heaters are sold in set sizes, so look at the nearest size above the result, and check mounting height, clearances, venting and the electrical or gas supply with the manufacturer and local rules.

Checking a heater you already have

Rearrange the formula to find the temperature rise a heater of a given output can deliver in your space:

Temperature rise = Output ÷ (Volume × 0.133)

Worked example: a 75,000 BTU/h heater in the starting space

Rise = 75,000 ÷ (16,800 × 0.133) = 75,000 ÷ 2,234.4 = 33.6°F

The heater would raise the space by about 34°F under the calculator’s rule of thumb, which is below the 40°F target. A larger heater, a lower target or better insulation would close the gap.

One heater or several

One large unit is simple, but several smaller units spread heat more evenly through a big or long space. For the 89,376 BTU/h starting result, two heaters would each need about 44,688 BTU/h and three about 29,792 BTU/h. Ask the manufacturer about the best layout and mounting height for your building.

Unit heater sizing rules of thumb compared

How the 0.133 factor lines up

The calculator multiplies 0.133 by the temperature rise, so a 40°F rise gives 0.133 × 40 = 5.32 BTU/h per cubic foot and a 30°F rise gives 0.133 × 30 = 3.99. Those sit close to the retailer’s 5 and 4, which suggests the two rules agree for typical cold and mild designs.

Worked comparison: a 24 ft by 30 ft shop with a 14 ft ceiling

The retailer’s example shop holds 24 × 30 × 14 = 10,080 ft³, and 10,080 ÷ 200 gives about 50,400 BTU/h. The calculator gives 10,080 × 0.133 × 40 = 53,626 BTU/h at a 40°F rise and 10,080 × 0.133 × 30 = 40,219 BTU/h at a 30°F rise.

Ceiling height, insulation and building type

The calculator counts ceiling height through the volume, but the retailer adds a margin on top for tall spaces and poorly insulated ones. Treat these as judgement calls and not as part of the formula.

Insulation and metal buildings

The same guide adds 10 to 25 percent for poor insulation and 25 to 40 percent for metal buildings. For the 89,376 BTU/h starting result, a 10 to 25 percent addition gives 98,314 to 111,720 BTU/h.

Air mixing and heater placement

Output is only part of the answer, because where the heat goes matters as well.

Why volume matters more than floor area

The retailer compares a 24 ft by 24 ft shop with an 8 ft ceiling, which holds 4,608 ft³, with the same floor at 14 ft, which holds 8,064 ft³. That is 75 percent more air to heat on an identical floor plan, which is why this calculator uses volume.

Frequently asked questions

How many BTU do I need for a unit heater?

Multiply the volume by 0.133 and by the temperature rise. A 40 ft by 30 ft space with a 14 ft ceiling and a 40°F rise needs 89,376 BTU/h.

What temperature rise should I use?

Use the gap between your coldest outdoor design temperature and the indoor temperature you want. A 30°F rise gives 3.99 BTU/h per cubic foot, close to the 4 used for mild climates.

Can I enter metres?

Yes. The dimension boxes convert other length units to feet before the calculation.