A boiler is sized by the heat your building loses, not by its floor area alone, but floor area times a climate factor is the usual first estimate. This boiler size calculator multiplies your heated area by a BTU/h per square foot figure for a mild, moderate or cold climate, or by a value you enter yourself.
Boiler Size Calculator
Recommended boiler output size for a home, from heated floor area and a BTU-per-square-foot factor for your climate.
The starting values are 2,000 ft² in a moderate climate, which gives 60,000 BTU/h.
How is boiler size calculated?
The calculator multiplies the heated area by a heat-loss factor in BTU/h per square foot. The factor comes from the climate setting unless you enter an override.
Boiler output (BTU/h) = Heated area × BTU/h per ft²
Where the climate defaults are 20 BTU/h per ft² for mild, 30 for moderate and 40 for cold. Entering a value in the override field replaces the climate default, and 0 means use the default.
Worked example: the starting values
Mild: 2,000 × 20 = 40,000 BTU/h
Moderate: 2,000 × 30 = 60,000 BTU/h
Cold: 2,000 × 40 = 80,000 BTU/h
The calculator’s own note describes 20 to 30 BTU/h per ft² as a rule of thumb and recommends a Manual J calculation for an exact load.
Worked examples for different homes
Worked examples
Output versus input rating
Boilers are listed by input as well as output. A boiler with a 100,000 BTU input at 80% efficiency delivers 100,000 × 0.80 = 80,000 BTU/h. To deliver the calculator’s 60,000 BTU/h at 80% you need an input of 60,000 ÷ 0.80 = 75,000 BTU/h.
How area and climate change the output
The table shows three heated areas at each climate default.
| Heated area | Mild (20) | Moderate (30) | Cold (40) |
|---|---|---|---|
| 1,200 ft² | 24,000 BTU/h | 36,000 BTU/h | 48,000 BTU/h |
| 2,000 ft² | 40,000 BTU/h | 60,000 BTU/h | 80,000 BTU/h |
| 3,000 ft² | 60,000 BTU/h | 90,000 BTU/h | 120,000 BTU/h |
Using the override
If you know the heat loss of your house per square foot, enter it in the override field. For 2,000 ft² at 35 BTU/h per ft² the result is 70,000 BTU/h, between the moderate and cold defaults. A heat loss calculation, or the one from an energy audit, is a better guide than a rule of thumb.
From output to input
Boilers are rated by input and by output, and the efficiency connects them. To deliver 60,000 BTU/h, an 80% efficient boiler needs an input of 75,000 BTU/h, a 90% efficient one needs about 66,700 and a 95% efficient one needs about 63,200. For the cold-climate 80,000 BTU/h at 85%, the input is about 94,100 BTU/h.
Why not simply buy a larger boiler
A boiler much larger than the load will reach temperature quickly, switch off and start again, and this short-cycling wastes fuel and wears the burner. A boiler close to the real load runs in longer cycles and holds the temperature more evenly. If you are between sizes, ask the installer to size the boiler from the heat loss and to say what margin they allow for the domestic hot water.
Frequently asked questions
How do I calculate boiler size?
Multiply the heated area by BTU/h per square foot. For 2,000 ft² at 30 that is 2,000 × 30 = 60,000 BTU/h.
How many BTU per square foot do I need?
Rules of thumb range from 25 to 35 for warm climates to 50 to 60 for cold climates, while this calculator uses 20, 30 and 40.
Is bigger better for a boiler?
No. Oversizing causes short-cycling, which wastes fuel and wears the equipment.
What is the difference between input and output?
Output is the heat delivered. A 100,000 BTU input boiler at 80% efficiency delivers 80,000 BTU/h.
What BTU per square foot should I use for a boiler?
The calculator uses 20, 30 and 40 for mild, moderate and cold climates. If you know your own heat loss, enter it in the override field.
How much input do I need for 60,000 BTU/h of output?
Divide by the efficiency. An 80% boiler needs 75,000 BTU/h of input and a 90% boiler needs about 66,700.
Does the boiler also heat my water?
Only if it is set up for it. Ask the installer how much extra capacity to allow for domestic hot water.