Radiant Tube Heater Sizing Calculator: Shop, Warehouse & Garage

A gas-fired radiant tube heater warms people and surfaces below it, and the output you need depends on the floor area, how high it is mounted and how often the space is used. This radiant tube heater sizing calculator multiplies the floor area by a BTU per hour rate for occasional or continuous use, then adds 15 percent when the ceiling or mounting height is over 14 feet. It starts with a 3,000 ft² shop, 16 ft high, in continuous use.

Heating & Cooling Sizing Calculators

Radiant Tube Heater Sizing Calculator

BTU output needed from a gas-fired radiant tube heater for a shop, warehouse or garage, by floor area and ceiling height.

How do you size a radiant tube heater?

Multiply the floor area by the BTU per hour per square foot for your use, then add 15 percent if the mounting height is above 14 ft.

Output = Floor area × BTU/h per ft² × Height factor

Where:

  • Floor area = square feet of the space
  • BTU/h per ft² = 25 for occasional use or 35 for continuous use, the values built into the calculator
  • Height factor = 1.15 if the height is over 14 ft, otherwise 1

Worked examples

Worked example: the calculator’s starting values

A 3,000 ft² shop, 16 ft high, in continuous use:

Output = 3,000 × 35 × 1.15 = 120,750 BTU/h

Worked example: a small garage, occasional use

A 600 ft² garage, 10 ft high, used occasionally:

Output = 600 × 25 × 1 = 15,000 BTU/h

Worked example: a tall warehouse

A 5,000 ft² warehouse, 18 ft high, in continuous use:

Output = 5,000 × 35 × 1.15 = 201,250 BTU/h

How do height and use change the answer?

For a 3,000 ft² space:

Use Height Output
Occasional 12 ft 75,000 BTU/h
Occasional 16 ft 86,250 BTU/h
Continuous 12 ft 105,000 BTU/h
Continuous 16 ft 120,750 BTU/h

The 15 percent increase applies only above 14 ft. At exactly 14 ft the factor is still 1, so a 3,000 ft² continuous-use space at 14 ft needs 105,000 BTU/h.

What a radiant tube heater does

A radiant tube heater burns gas inside a long tube that glows with heat and sends infrared warmth down to the floor, equipment and people, rather than only warming the air. That is why it is often used in shops, warehouses and garages with high ceilings, where heating all the air would waste energy. Installation details such as mounting height and clearances come from the manufacturer.

Occasional and continuous use compared

Occasional use suits a space that is heated only while you work in it. Continuous use means the space is kept warm for long periods. The calculator uses a higher BTU per square foot for continuous use so the system can hold the temperature. The two rates, 25 and 35, are built-in assumptions, not code requirements.

What the radiant tube heater sizing calculator leaves out

It does not use your climate, insulation level, door openings, window area or the temperature you want, which all affect real heat loss. It gives a starting output figure, not a full heat loss calculation. A manufacturer or a heating contractor can check the result against your building and select a model and tube layout.

Choosing a model from the result

Compare the output figure with the input rating of heaters on offer, and ask whether one large unit or several smaller ones suit the layout. Spreading heat over several units can help in a long or wide space. Confirm clearances, venting and gas supply requirements with the manufacturer and your local rules.

Floor area and output compared

At a mounting height of 12 ft, so no height increase:

Floor area Occasional use Continuous use
1,500 ft² 37,500 BTU/h 52,500 BTU/h
2,000 ft² 50,000 BTU/h 70,000 BTU/h
3,000 ft² 75,000 BTU/h 105,000 BTU/h
4,000 ft² 100,000 BTU/h 140,000 BTU/h

Worked example: a tall workshop used occasionally

A 2,000 ft² workshop with a 20 ft mounting height, used occasionally:

Output = 2,000 × 25 × 1.15 = 57,500 BTU/h

Measuring an L-shaped floor area

Split the floor into rectangles and add them. A main area of 60 ft by 40 ft and a side wing of 20 ft by 30 ft give 2,400 + 600 = 3,000 ft², which is the same as the starting example.

Splitting the output between several heaters

Divide the total by the number of units. For the starting result, three heaters would each need about 120,750 ÷ 3 = 40,250 BTU/h. In kilowatts, 120,750 BTU/h is about 35.4 kW (120,750 ÷ 3,412). Ask the manufacturer how many units and what tube lengths suit your layout.

Mounting height and row spacing

Height affects both the BTU you need and where the tubes go.

Frequently asked questions

How many BTU do I need for a radiant tube heater?

The calculator uses 25 BTU/h per ft² for occasional use and 35 for continuous use, plus 15 percent above 14 ft. No published rule confirms those rates, so check with a manufacturer.

Does the calculator account for insulation?

No. It uses floor area, use and height only, so a poorly insulated building needs a contractor’s heat loss figure.