A garage heater has to warm the whole volume of the space, and how much heat that takes depends on the insulation and on how far you want to raise the temperature. This garage heater size calculator multiplies the garage volume by a BTU per hour factor for the insulation level, then by a multiplier for the temperature rise you want. It starts with a 24 ft by 24 ft garage with a 10 ft ceiling, average insulation and a moderate rise of 30°F.
Garage Heater Size Calculator
Recommended heater size for a garage, from its volume, insulation level and a garage furnace or space heater.
How do you size a garage heater?
Multiply the volume in cubic feet by the insulation factor and the temperature-rise multiplier. The calculator works from volume rather than floor area, so a taller ceiling raises the result, and the two tables below show the built-in values it uses.
Volume = Length × Width × Ceiling height
Output = Volume × Insulation factor × Rise multiplier
The calculator uses these built-in values:
| Insulation | Factor (BTU/h per ft³) |
|---|---|
| Poor or uninsulated | 3 |
| Average | 2 |
| Well insulated | 1.3 |
| Temperature rise | Multiplier |
|---|---|
| Moderate, +30°F | 1 |
| Large, +50°F | 1.4 |
These are the calculator’s assumptions. Its own note calls the result a starting estimate and not a replacement for a proper heat-loss calculation.
Worked examples
Worked example: the starting values
A 24 ft by 24 ft garage, 10 ft ceiling, average insulation, +30°F:
Volume = 24 × 24 × 10 = 5,760 ft³
Output = 5,760 × 2 × 1 = 11,520 BTU/h
Worked example: an uninsulated garage with a large rise
The same garage with poor insulation and a +50°F rise:
Output = 5,760 × 3 × 1.4 = 24,192 BTU/h
Worked example: a smaller one-car garage
A 12 ft by 20 ft garage with an 8 ft ceiling, poor insulation, +30°F:
Volume = 12 × 20 × 8 = 1,920 ft³
Output = 1,920 × 3 × 1 = 5,760 BTU/h
Insulation level and temperature rise compared
For the 5,760 ft³ starting garage:
| Insulation | +30°F | +50°F |
|---|---|---|
| Poor | 17,280 BTU/h | 24,192 BTU/h |
| Average | 11,520 BTU/h | 16,128 BTU/h |
| Well insulated | 7,488 BTU/h | 10,483 BTU/h |
Insulation has a bigger effect than the extra rise, so improving it can let you buy a smaller heater.
BTU to watts conversion for electric garage heaters
An electric heater turns each kilowatt-hour into 3,412 Btu, according to the U.S. Energy Information Administration’s conversion table. So 11,520 BTU/h is 11,520 ÷ 3.412, about 3,376 W. Gas heaters are rated in BTU per hour directly.
What the garage heater size calculator leaves out
The calculator does not use your climate, the outdoor design temperature, the garage door’s insulation, air leaks, windows or the floor slab. These all change real heat loss. A big uninsulated door can need more heat than the formula gives. For a firm number, ask a heating contractor for a heat-loss calculation.
How do you choose between heater types?
Match the output to the result, then think about fuel, venting and where you can place the unit. A gas heater needs safe venting, and electric heaters need a suitable circuit. Follow the manufacturer’s clearances and local rules, and do not use an unvented fuel-burning heater in a closed garage.
How do you plan a garage heater step by step?
Work through the inputs in order and write each one down before you use the calculator, because a garage heater size depends on four things: the volume, the insulation, the temperature rise and the heater you can fit.
- Measure the length, width and ceiling height, then multiply them to get the volume in cubic feet.
- Pick the insulation level that best describes the walls, ceiling and garage door.
- Choose the temperature rise from the outdoor temperature in your coldest weeks and the indoor temperature you want.
- Read the BTU per hour result, then look at heaters rated at or just above it.
Worked examples
Worked example: a two-car garage with a high ceiling
A 22 ft by 22 ft garage with a 12 ft ceiling, average insulation and a +50°F rise:
Volume = 22 × 22 × 12 = 5,808 ft³
Output = 5,808 × 2 × 1.4 = 16,262 BTU/h
Worked example: a well-insulated workshop
A 16 ft by 20 ft workshop with a 9 ft ceiling, well insulated, +30°F:
Volume = 16 × 20 × 9 = 2,880 ft³
Output = 2,880 × 1.3 × 1 = 3,744 BTU/h
Watts = 3,744 ÷ 3.412 = about 1,097 W
Garage size and heater output compared
With average insulation and a +30°F rise, the output is the volume times 2:
| Garage size | Volume | Output |
|---|---|---|
| 12 ft × 20 ft, 8 ft ceiling | 1,920 ft³ | 3,840 BTU/h |
| 20 ft × 20 ft, 9 ft ceiling | 3,600 ft³ | 7,200 BTU/h |
| 24 ft × 24 ft, 10 ft ceiling | 5,760 ft³ | 11,520 BTU/h |
| 30 ft × 30 ft, 10 ft ceiling | 9,000 ft³ | 18,000 BTU/h |
Garage heater size by number of cars
With average insulation, an 8 ft ceiling and a +30°F rise, this calculator gives about 2,880 to 4,608 BTU/h for a one-car garage, 7,040 to 9,600 for a two-car garage and 10,400 to 12,320 for a three-car garage. Colder climates need more, as the next sections explain.
Why do other garage heater guides quote bigger numbers?
The gap is the missing climate input. Treat the calculator result as the floor for a cold region and ask for a heat-loss calculation before you buy a heater near that number.
Climate zone, attached garages and temperature rise
How do you work out the temperature rise?
Subtract the coldest outdoor temperature you expect from the indoor temperature you want.
Temperature rise = Desired indoor temperature − Outdoor winter low
NewAir’s example is 65°F indoors against a 15°F low, a 50°F rise. In this calculator that is the +50°F option, which multiplies the result by 1.4. A rise nearer 30°F uses the +30°F option.
Heater types by climate
Gas and propane heaters
These are rated in BTU per hour, so the calculator result compares with the label directly. They need safe venting and the manufacturer’s clearances.
Electric heaters
Electric heaters are rated in watts. Divide the BTU per hour by 3.412 for watts, so a 50,000 BTU/h heater is about 14,654 W, close to 15 kW. That is a large electrical load, so confirm the circuit with an electrician before you commit.
Frequently asked questions
How many BTU do I need to heat a two-car garage?
For 440 to 600 ft² with an 8 ft ceiling, average insulation and a +30°F rise, the calculator gives 7,040 to 9,600 BTU/h. A cold climate, poor insulation or a +50°F rise raises that.
How many BTU per square foot does a garage need?
The calculator works from volume. At an 8 ft ceiling, average insulation and +30°F it is 16 BTU/h per ft², and poor insulation with +50°F is 33.6. NewAir quotes a wider rule of thumb of 30 to 60 BTU per ft².
How do I convert BTU to watts?
Divide BTU per hour by 3.412. A result of 11,520 BTU/h is about 3,376 W.
What temperature rise should I choose?
Subtract your coldest expected outdoor temperature from the indoor temperature you want. 65°F against a 15°F low is a 50°F rise, so choose +50°F.
Should I round up to the next heater size?
Heaters come in set sizes, so choose one at or just above the result and check with the manufacturer. In a cold region, size from a heat-loss calculation instead.