Radiator output is the room area, scaled for ceiling height, times a heat factor for how well the room is insulated, and this heating radiator size calculator returns the result in BTU per hour. Enter the room area and ceiling height, pick Poor, Average or Good for insulation and windows, and the calculator gives a recommended output to compare with radiator ratings. The heat factors are the calculator’s built-in assumptions, so treat the answer as a starting estimate.
Heating Radiator Size Calculator
Radiator output (BTU/h) needed for a room, from room area, ceiling height and insulation.
How do you calculate radiator size for a room?
Multiply the floor area by the ceiling height divided by 8 ft, then by the BTU/h per square foot for your insulation level. The height term scales the 8 ft baseline up or down, so a taller room asks for more output.
Radiator output (BTU/h) = Area × (Ceiling height ÷ 8) × BTU/h per ft²
Where:
- Area = floor area of the room in square feet
- Ceiling height = in feet; 8 ft is the baseline
- BTU/h per ft² = 35 for Poor, 25 for Average, 18 for Good insulation and windows
Worked examples
Worked example: an average room
A 150 ft² room with an 8 ft ceiling and average insulation and windows:
Output = 150 × (8 ÷ 8) × 25 = 3,750 BTU/h
Worked example: a taller, draughtier room
A 200 ft² room with a 9 ft ceiling and poor insulation and windows:
Output = 200 × (9 ÷ 8) × 35 = 200 × 1.125 × 35 = 7,875 BTU/h
Insulation level and output compared
Insulation sets the heat factor, so it has the largest effect on the result. For the same 150 ft² room with an 8 ft ceiling:
| Insulation and windows | Factor (BTU/h per ft²) | Recommended output |
|---|---|---|
| Poor | 35 | 5,250 BTU/h |
| Average | 25 | 3,750 BTU/h |
| Good | 18 | 2,700 BTU/h |
The calculator does not tell you which category your room is in. Pick the one that matches your walls and windows: older single-glazed windows and little wall insulation point to Poor, while modern double or triple glazing with good wall insulation points to Good.
Converting BTU/h to watts
Many radiators are rated in watts. One watt is 3.412 BTU/h, so divide the BTU/h figure by 3.412.
Watts = BTU/h ÷ 3.412
The average room above needs 3,750 ÷ 3.412 = about 1,099 W, the draughty room 7,875 ÷ 3.412 = about 2,308 W, and the well-insulated room 2,160 ÷ 3.412 = about 633 W (for 120 ft² at 8 ft).
Choosing a radiator from the result
Radiators come in fixed output sizes, so pick one at or just above the recommended output. A slightly larger radiator can be turned down, while a smaller one may not warm the room. Check the rating at the water temperature your system runs at, because manufacturers publish output for specific conditions.
Splitting the output between two radiators
If one wall cannot take a single large radiator, divide the total between two. For 7,875 BTU/h you could fit two radiators of about 3,940 BTU/h each. Place them where the room loses the most heat, usually under windows or on exterior walls.
What the heating radiator size calculator leaves out
The calculator uses area, height and one insulation setting. It does not account for how many walls are exterior, window size, a fireplace or other heat source, or the temperature you want. For a corner room or one with large windows, sizing up is sensible. If another heat source covers part of the load, you can size toward the lower end.
Ceiling height, room area and output compared
For a room with average insulation and windows (25 BTU/h per ft²), 150 ft²:
| Ceiling height | Output |
|---|---|
| 8 ft | 3,750 BTU/h |
| 9 ft | 4,219 BTU/h |
| 10 ft | 4,688 BTU/h |
| 12 ft | 5,625 BTU/h |
With an 8 ft ceiling and average insulation, area changes the output like this:
| Room area | Output |
|---|---|
| 100 ft² | 2,500 BTU/h |
| 150 ft² | 3,750 BTU/h |
| 200 ft² | 5,000 BTU/h |
| 300 ft² | 7,500 BTU/h |
Worked example: a well-insulated room with a tall ceiling
A 180 ft² room with a 9 ft ceiling and good insulation and windows:
Output = 180 × (9 ÷ 8) × 18 = 180 × 1.125 × 18 = 3,645 BTU/h
Watts = 3,645 ÷ 3.412 = about 1,068 W
Sizing radiators for several rooms
Run the calculator once for each room, since each room has its own area, height and insulation. Add the results only if you need a figure for the whole system, such as for the boiler. For the three rooms above (3,750, 7,875 and 2,160 BTU/h):
Total = 3,750 + 7,875 + 2,160 = 13,785 BTU/h
Watts = 13,785 ÷ 3.412 = about 4,040 W
Choose each radiator for its own room rather than splitting the total evenly.
Where the methods differ
The calculator and the volume method agree for an average room, but they treat glazing and insulation differently.
Frequently asked questions
How many BTU do I need to heat a room?
Multiply the area by the ceiling height divided by 8 ft and by 35, 25 or 18 for Poor, Average or Good insulation. A 150 ft² room at 8 ft with average insulation needs 3,750 BTU/h.
How do I convert BTU/h to watts?
Divide by 3.412. The average 150 ft² room needs 3,750 ÷ 3.412, about 1,099 W.
Does insulation change the radiator size?
Yes. For the same 150 ft² room the calculator gives 5,250 BTU/h for Poor, 3,750 for Average and 2,700 for Good insulation and windows.