The first number you need for a heat exchanger is its duty, the rate of heat it has to transfer. This heat exchanger sizing calculator finds the required duty in BTU per hour from the water flow rate in gallons per minute and the temperature drop across the exchanger in degrees Fahrenheit. It starts with 10 GPM and a 20°F drop.
Heat Exchanger Sizing Calculator
Required heat exchanger duty (BTU/h) from flow rate and the temperature drop across it — for hydronic, radiant or pool heat exchangers.
How do you calculate heat exchanger duty?
Multiply the flow rate by 500 and by the temperature drop. The result is the duty, the heat the exchanger must move, in BTU per hour, and every variable is explained under the formula.
Duty (BTU/h) = Flow (GPM) × 500 × Temperature drop (°F)
Where:
- Flow = gallons per minute of water through the exchanger
- 500 = pounds of water per gallon (8.33) × 60 minutes per hour × 1 BTU per pound per °F
- Temperature drop = the difference between the water going in and coming out, in °F
The 500 is the calculator’s constant for plain water. It works as a quick rule for water-based systems and does not suit other fluids.
Worked examples
Worked example: the starting values
Duty = 10 × 500 × 20 = 100,000 BTU/h
Worked example: a larger hydronic loop
A loop with 25 GPM and a 15°F drop:
Duty = 25 × 500 × 15 = 187,500 BTU/h
Worked example: a small radiant zone
A zone with 6 GPM and a 10°F drop:
Duty = 6 × 500 × 10 = 30,000 BTU/h
Flow and duty compared
At a 20°F drop:
| Flow | Duty |
|---|---|
| 5 GPM | 50,000 BTU/h |
| 10 GPM | 100,000 BTU/h |
| 20 GPM | 200,000 BTU/h |
| 40 GPM | 400,000 BTU/h |
Duty rises in a straight line with both flow and temperature drop.
How do you convert the duty to other units?
One kilowatt is about 3,412 BTU/h, so 100,000 BTU/h is about 29.3 kW. A ton of capacity is 12,000 BTU/h, so the same duty is about 8.3 tons. Use the two formulas below for any other duty.
kW = BTU/h ÷ 3,412
Tons = BTU/h ÷ 12,000
Where is this used?
The calculator suits hydronic heating, radiant systems and pool heating, where water carries heat from one loop to another. The flow and temperature drop come from your system design or from measurements on the loop.
What the heat exchanger sizing calculator leaves out
Duty is only the first step in choosing an exchanger. The calculator does not account for the temperature on the other side, the approach temperature, the area or type of exchanger, fluid mixtures such as glycol, or pressure drop. Manufacturers use these to select a model, so give them the duty, the flow rates and the supply and return temperatures on both sides.
How do you pick a heat exchanger from the duty?
Send the duty with the fluid types, flow rates, temperatures and pressure limits to the manufacturer or a supplier. They will match a model and size. Leave some margin if the duty may rise later, and ask what the rating assumes.
How do you rearrange the duty formula?
The same formula can be turned around when you know the duty and want the flow or the temperature drop. Divide the duty by 500 times the other variable, as the two lines below show.
Flow (GPM) = Duty ÷ (500 × Temperature drop)
Temperature drop (°F) = Duty ÷ (500 × Flow)
Worked examples
Worked example: finding the flow
A system needs 120,000 BTU/h with a 20°F drop:
Flow = 120,000 ÷ (500 × 20) = 12 GPM
Worked example: finding the temperature drop
The starting loop carries 10 GPM and transfers 100,000 BTU/h:
Drop = 100,000 ÷ (500 × 10) = 20°F
The calculator itself takes flow and drop as inputs and gives duty, so use these rearranged forms to check a design by hand or to decide which numbers to try.
Temperature drop and duty compared
At the starting flow of 10 GPM:
| Temperature drop | Duty |
|---|---|
| 10°F | 50,000 BTU/h |
| 20°F | 100,000 BTU/h |
| 30°F | 150,000 BTU/h |
| 40°F | 200,000 BTU/h |
Worked example: a pool loop
A loop with 30 GPM and a 10°F drop:
Duty = 30 × 500 × 10 = 150,000 BTU/h
Duty values in kW and tons
| Duty | kW | Tons |
|---|---|---|
| 50,000 BTU/h | 14.7 kW | 4.2 tons |
| 100,000 BTU/h | 29.3 kW | 8.3 tons |
| 200,000 BTU/h | 58.6 kW | 16.7 tons |
What numbers should you gather before you call a supplier?
Have the duty, the flow rate and the inlet and outlet temperatures on both sides of the exchanger. Add the fluid on each side, the pressure limits and any space limits. With these, a supplier can check the calculator’s duty against their own selection and tell you which models fit.
The 500 constant and glycol mixtures
The 500 comes from water: 8.33 pounds per gallon times 60 minutes per hour times a specific heat of 1.0. MEP Academy points out that glycol mixtures carry less heat per gallon and suggests roughly 485 for a light mixture, 470 for a medium one and 450 for a heavy one.
How much does glycol change the duty?
The calculator uses 500, so it overstates the duty of a glycol loop. For 4 GPM at a 20°F drop, 500 gives 40,000 BTU/h, 485 gives 38,800 and 450 gives 36,000.
What should you do with a glycol loop?
Treat the result as an upper estimate and give the supplier the real mixture. They size from the fluid properties, not from the water constant.
Sizing from a tank or pool volume instead of a flow
Sometimes you know how much water you must heat, not the flow. Work out the heat first, then spread it over the hours you can wait.
How much heat does a volume of water need?
Heat (BTU) = Gallons × 8.34 × Temperature rise
As an example, 600 gallons heated 30°F needs about 150,000 BTU. The exact product is 600 × 8.34 × 30 = 150,120 BTU.
How do you turn that heat into a flow?
Divide the heat by the hours you allow, then use the calculator’s formula in reverse. Over 6 hours the duty is 150,120 ÷ 6 = 25,020 BTU/h. At a 20°F drop the flow is 25,020 ÷ (500 × 20), about 2.5 GPM.
Quick reference: BTU per hour for each GPM
Because the duty is 500 times the flow times the drop, every 1 GPM carries a fixed amount of heat at each temperature drop.
| Temperature drop | BTU/h for 1 GPM | Flow for 100,000 BTU/h |
|---|---|---|
| 10°F | 5,000 | 20 GPM |
| 15°F | 7,500 | 13.3 GPM |
| 20°F | 10,000 | 10 GPM |
| 25°F | 12,500 | 8 GPM |
MEP Academy makes the same point about pipe size: 100,000 BTU/h needs 20 GPM at a 10°F drop but only 10 GPM at 20°F, so a smaller drop means more flow.
Boiler output and pressure drop limit a real exchanger
A duty from the calculator does not guarantee the exchanger will deliver it. The boiler output is the real limit, and the pressure drop through the exchanger is a main sizing check, along with the flow rate and temperatures on both sides. If the boiler cannot supply the duty, a larger exchanger will not help.
What to check before you buy
Compare the duty with the boiler or heat pump output, then ask the supplier for the pressure drop at your flow so the circulator can be matched.
Frequently asked questions
How do I size a heat exchanger from GPM and temperature drop?
Multiply the flow in GPM by 500 and by the temperature drop in °F. For 10 GPM at a 20°F drop the duty is 100,000 BTU/h.
Why is the constant 500 in the formula?
It is 8.33 pounds per gallon times 60 minutes per hour times a specific heat of 1.0 for water, which is 499.8, rounded to 500.
Does glycol change the heat exchanger calculation?
Yes. A glycol mixture carries less heat per gallon, and MEP Academy suggests roughly 485, 470 or 450 in place of 500. The calculator uses 500, so treat its result as an upper estimate.
How many GPM do I need for a given load?
Divide the load by 500 times the temperature drop. A 32,000 BTU/h load at a 20°F drop needs 3.2 GPM.
How do I convert heat exchanger duty to kW or tons?
Divide BTU/h by 3,412 for kW or by 12,000 for tons. A duty of 100,000 BTU/h is about 29.3 kW or 8.3 tons.
Does a smaller temperature drop need more flow?
Yes. For 100,000 BTU/h you need 20 GPM at a 10°F drop but 10 GPM at 20°F.