A greenhouse heater is sized from three things: how much covered surface the greenhouse has, what it is covered with, and how far above the outside air you want to hold the inside. This greenhouse heat calculator multiplies them to give the heater output you need in BTU/h. Enter the covered area (walls plus roof), choose the glazing type and set the temperature difference.
Greenhouse Heat Calculator
BTU/h heater output needed for a greenhouse, from covered surface area, glazing type and desired temperature difference.
The starting values are 500 ft² of covering, single-layer poly or glass, and a 40°F difference, which give 24,000 BTU/h.
How do you size a greenhouse heater?
Multiply the covered surface area by the temperature difference and by a heat-loss factor for the glazing. Purdue’s greenhouse heating guide writes it as Q = U × A × ΔT.
Output (BTU/h) = Covered area (ft²) × Temperature difference (°F) × U
Where the area is every wall and roof surface that is covered, the temperature difference is the inside setpoint minus the coldest outside temperature, and U is the heat-loss factor in BTU/h per ft² per °F.
Worked example: the starting values
Output = 500 × 40 × 1.2 = 24,000 BTU/h
Dividing by 3,412 BTU per kWh gives 24,000 ÷ 3,412 = 7.03 kW of electric heating for the same output.
The three glazing options
The calculator has three factors. The table shows the output each one gives for 500 ft² at a 40°F difference.
| Glazing in the calculator | U | Output at 500 ft² and 40°F |
|---|---|---|
| Single-layer poly or glass | 1.2 | 24,000 BTU/h |
| Double-layer poly | 0.7 | 14,000 BTU/h |
| Insulated polycarbonate | 0.5 | 10,000 BTU/h |
How do the calculator’s factors compare with published figures?
Purdue gives 0.55 for double polycarbonate, 0.70 for double polyethylene, about 1.2 for single polythene, and 0.5 for double polythene with an infrared blocker. The University of Wyoming extension uses a similar constant, K: 1.4 for single polyethylene or fiberglass, 1.8 for single glass and 1.0 for a double layer, in windy areas.
| Calculator option | Calculator U | Published figure |
|---|---|---|
| Single-layer poly or glass | 1.2 | Purdue: about 1.2 for single polythene. Wyoming: 1.4 poly, 1.8 glass |
| Double-layer poly | 0.7 | Purdue: 0.70. Wyoming: 1.0 windy, 0.8 non-windy |
| Insulated polycarbonate | 0.5 | Purdue: 0.55 double polycarbonate, 0.5 double poly with IR blocker |
The double-layer and polycarbonate factors line up with Purdue. The single-layer factor of 1.2 matches Purdue’s single polythene but is below Wyoming’s 1.4 for poly and 1.8 for glass. For a glass greenhouse that is a real gap: 500 × 40 × 1.8 = 36,000 BTU/h, which is 12,000 BTU/h or one third more than the calculator’s 24,000. If your covering is glass, size up or compare the result with the 1.8 figure.
Windy and sheltered sites
The calculator has no wind input. Wyoming’s constants are for windy areas, and it says the factor would be about 0.2 less where the greenhouse is not exposed to wind. That makes single glass 1.6, single poly 1.2 and a double layer 0.8.
How do you measure the covered surface area?
Add up every covered surface, which is the walls and the roof. Leave out the floor, because the calculator’s input is walls plus roof.
Worked example: a 12 ft by 20 ft greenhouse
Take a greenhouse with 6 ft walls and two roof slopes that are each 7 ft long. The two long walls are 2 × (20 × 6) = 240 ft² and the two ends are 2 × (12 × 6) = 144 ft², so the walls total 384 ft². The roof is 2 × (7 × 20) = 280 ft². The covered area is 384 + 280 = 664 ft². The gable triangles in the end walls are ignored, so measure your own shape if it has them.
Worked examples for different greenhouses
Worked examples
Double poly at a 40°F difference
For the 664 ft² greenhouse, 664 × 40 × 0.7 = 18,592 BTU/h. Divided by 3,412 that is about 5.45 kW, or roughly 5,449 W of electric heating.
The same greenhouse in glass
With the calculator’s 1.2 the output is 664 × 40 × 1.2 = 31,872 BTU/h. With Wyoming’s 1.8 for single glass it is 664 × 40 × 1.8 = 47,808 BTU/h, which is 15,936 BTU/h more.
Changing the temperature difference
The difference is inside minus outside, so holding 55°F when it is 15°F outside is 55 − 15 = 40°F. For 500 ft² of double poly the output is 10,500 BTU/h at 30°F, 14,000 at 40°F and 17,500 at 50°F. A lower setpoint is the cheapest way to cut the heater size.
What the calculator leaves out
It does not add a wind or air-leakage allowance, a safety margin, ground heat loss or the heater’s efficiency. Neither Purdue nor Wyoming gives a safety factor, so any margin is your decision. When you pick a heater, compare its rated output with the result.
Frequently asked questions
How do I calculate the heater size for a greenhouse?
Multiply the covered area in ft² by the temperature difference in °F and by the U factor. 500 ft² at 40°F with a factor of 1.2 gives 24,000 BTU/h.
What U value should I use for glass?
The calculator uses 1.2 for single-layer poly or glass. The University of Wyoming extension gives 1.8 for single glass in windy areas, so consider a higher figure for glass.
What area do I enter?
The covered surface: all walls plus the roof. A 12 ft by 20 ft greenhouse with 6 ft walls and two 7 ft roof slopes has 384 + 280 = 664 ft².
How do I convert BTU/h to watts?
Divide by 3,412 to get kilowatts. 18,592 BTU/h is about 5.45 kW.
Does the calculator include wind?
No. Wyoming says the factor is about 0.2 lower on a site that is not windy, so the result is a middle estimate.
How can I reduce the heater size I need?
Lower the temperature difference, or cover with a better glazing. Double poly at 0.7 needs 14,000 BTU/h against 24,000 for single poly on the same 500 ft² at 40°F.