This sensible heat ratio calculator divides the sensible heat gain by the total of sensible and latent heat gain to give the SHR used in HVAC work. Enter the two loads in BTU per hour, and it returns the ratio to three decimal places. A higher ratio means that more of the cooling load is dry heat and less of it is moisture.
Sensible Heat Ratio Calculator
Sensible heat ratio (SHR) for an HVAC load, from sensible and latent heat gains.
Starting values: a sensible heat gain of 24,000 BTU/h and a latent heat gain of 6,000 BTU/h give a total of 30,000 BTU/h and a sensible heat ratio of 0.800.
How to use the calculator
- Enter the sensible heat gain in BTU per hour.
- Enter the latent heat gain in BTU per hour, in the same unit.
- Read the sensible heat ratio.
The ratio is a fraction between 0 and 1, so it has no unit. If both loads are zero, the calculator shows 0.
The formula
SHR = Sensible heat / (Sensible heat + Latent heat)
Where:
- Sensible heat = heat that changes the air temperature
- Latent heat = heat tied up in moisture, which changes humidity without changing the temperature
- Sensible heat + Latent heat = the total heat gain
You can rearrange it to find the loads when you know the ratio and the total. Sensible = SHR × Total, and Latent = Total – Sensible.
Worked examples
Example 1: the default loads
The total is 24,000 + 6,000 = 30,000 BTU/h. The SHR is 24,000 / 30,000 = 0.800. Of every 10 units of heat, 8 are sensible and 2 are latent.
Example 2: more moisture
With 18,000 BTU/h of sensible heat and 6,000 BTU/h of latent heat, the total is 24,000 and the SHR is 0.750. More of the load is moisture than in example 1, so the ratio is lower.
Example 3: a mostly dry load
With 9,000 sensible and 1,000 latent, the total is 10,000 and the SHR is 0.900.
Example 4: an equal split
With 15,000 sensible and 15,000 latent, the SHR is 0.500. Half of the load is sensible and half is latent.
Example 5: finding the loads from a ratio
If a system has a total load of 30,000 BTU/h and an SHR of 0.8, the sensible load is 0.8 × 30,000 = 24,000 BTU/h and the latent load is 6,000 BTU/h. A total of 30,000 BTU/h is 2.5 tons of cooling, since one ton of cooling is 12,000 BTU/h.
What the ratio tells you
A high SHR means that the load is mostly sensible heat, so the equipment is mainly cooling the air. A low SHR means that a large share of the load is moisture, such as from people, cooking or humid outside air, so the equipment must also remove water vapour. The ratio matters when you choose or check equipment, because cooling equipment has its own ratio of sensible to total capacity. Compare the ratio you need with the figure for the equipment on the manufacturer’s data sheet.
Sensible and latent heat
Sensible heat is the heat you can measure with a thermometer. Latent heat is the energy involved in changing water between vapour and liquid, which shows up as humidity. The two together make up the total cooling load. The calculator does not work out either load for you. It uses the figures from a load calculation, a design report or a measurement.
Common mistakes
- Mixing units. Both loads must be in the same unit, such as BTU/h, or watts.
- Using the total in place of the sensible load. The first box takes the sensible heat only.
- Reading the SHR as a percentage. A result of 0.800 means 80%.
- Applying the ratio to the wrong operating condition. Sensible and latent loads change with the weather, so use the loads that match the condition you are checking.
Limits
The calculator divides two numbers and gives the ratio. It does not calculate heat gains, size equipment, or tell you what ratio a building needs. For those tasks, use a load calculation method and the manufacturer’s data.
Using watts instead of BTU per hour
The ratio does not depend on the unit, so you can enter both loads in watts or kilowatts and get the same answer. To convert, one BTU per hour is about 0.293 watts. The default 24,000 BTU/h of sensible heat is about 7.03 kW, and 6,000 BTU/h of latent heat is about 1.76 kW. The ratio is 7.03 / (7.03 + 1.76) = 0.800 either way.
Checking a design
When you have a load calculation, take the sensible and the latent figure for the same design condition and enter them. Then compare the SHR with the value that the equipment can deliver at that condition, from the manufacturer’s data. If the equipment removes less moisture than the load needs, the space can end up humid even when the temperature is on target. The calculator gives you the number to compare. The data sheet gives you the equipment side of the comparison.
Working on something related? Try the A/G ratio calculator, diamond ratio calculator or meat to fat ratio calculator.
Frequently asked questions
How do I calculate the sensible heat ratio?
Divide the sensible heat gain by the sum of the sensible and latent heat gains. For 24,000 and 6,000 BTU/h, the SHR is 0.800.
What does a low SHR mean?
A larger share of the load is latent heat, which is moisture, so the system must remove more water vapour.
Can I use watts instead of BTU per hour?
Yes, if both loads use the same unit. The ratio has no unit.
How do I find the sensible load from the SHR?
Multiply the SHR by the total heat gain. For 0.8 and 30,000 BTU/h, the sensible load is 24,000 BTU/h.
Does the calculator size my equipment?
No. It gives the ratio from the two loads you enter.