This LMTD calculator finds the log mean temperature difference of a heat exchanger for counter-flow and parallel-flow arrangements, applies the correction factor for a one-shell, two-pass shell-and-tube exchanger, and uses the result to size the heat transfer area from Q = U x A x LMTD.
LMTD Calculator
Log mean temperature difference for counter-flow, parallel-flow or shell-and-tube heat exchangers, with the correction factor F and heat transfer area.
Starting values: the calculator opens with a hot stream cooling from 100 to 60 and a cold stream heating from 20 to 50. The counter-flow LMTD is 44.81 K and the parallel-flow LMTD is 33.66 K.
The formula
LMTD = (dT1 – dT2) / ln(dT1 / dT2)
Where dT1 and dT2 are the temperature differences between the hot and cold streams at the two ends of the exchanger:
- Counter-flow: dT1 = Thi – Tco and dT2 = Tho – Tci.
- Parallel flow: dT1 = Thi – Tci and dT2 = Tho – Tco.
Here Thi and Tho are the hot-side inlet and outlet temperatures, and Tci and Tco are the cold-side inlet and outlet temperatures. If the two differences are equal, the formula is 0 / 0 and the LMTD is simply that common difference. Use the same temperature unit for all four values, because only differences matter.
Worked examples
Example 1: counter-flow
With Thi = 100, Tho = 60, Tci = 20 and Tco = 50, the end differences are 100 – 50 = 50 and 60 – 20 = 40. The LMTD is (50 – 40) / ln(50 / 40) = 10 / 0.2231 = 44.81 K.
Example 2: parallel flow
With the same four temperatures, the end differences are 100 – 20 = 80 and 60 – 50 = 10. The LMTD is (80 – 10) / ln(8) = 70 / 2.079 = 33.66 K. Counter-flow gives the larger mean difference for the same duty, so it needs less area. That is why counter-flow is the preferred arrangement where it is practical.
Example 3: shell-and-tube correction
For a one-shell, two-pass exchanger, the calculator applies a correction factor F. First compute R = (Thi – Tho) / (Tco – Tci) = 40 / 30 = 1.333 and P = (Tco – Tci) / (Thi – Tci) = 30 / 80 = 0.375. For these values F = 0.8906, so the effective difference is 44.81 x 0.8906 = 39.91 K.
Example 4: sizing the area
The heat duty equation is Q = U x A x LMTD, so A = Q / (U x LMTD). With Q = 500 kW and U = 800 W per square meter per kelvin, the counter-flow area is 500,000 / (800 x 44.81) = 13.95 square meters. For the shell-and-tube case, using 39.91 K, the area is 500,000 / (800 x 39.91) = 15.66 square meters. The correction factor costs about 12% more area.
When LMTD is the right method
LMTD suits cases where all four temperatures are known, which is the usual situation when you are sizing an exchanger. If you only know the inlet temperatures, the effectiveness-NTU method is easier, because it does not need the outlet temperatures in advance.
Assumptions
- The overall coefficient U is constant along the exchanger.
- Specific heats are constant, and there is no heat loss to the surroundings.
- There is no phase change, or the temperature of the stream that changes phase is constant.
Where these do not hold, the result is an approximation, and a more detailed design method is needed.
Tips
- Check that the temperature differences at both ends are positive. A negative one means a temperature cross, which a simple exchanger cannot do.
- A low correction factor is a warning that the arrangement is inefficient, so consider adding shells or changing the layout.
- Keep units consistent for U, Q and area.
Reading R and P
The two parameters used for the correction factor describe the exchanger. R is the ratio of the hot-side temperature change to the cold-side change, which is the same as the ratio of the heat capacity rates. P is the fraction of the maximum possible cold-side temperature rise that is actually achieved. Both are dimensionless, so you can enter temperatures in any consistent unit. In the default case, R is 1.333 because the hot stream falls by 40 while the cold stream rises by 30, and P is 0.375 because the cold stream gains 30 of the 80 available.
A quick sanity check
The LMTD always lies between the two end differences. In the counter-flow example, 44.81 is between 40 and 50, and in the parallel example, 33.66 is between 10 and 80. It is also always lower than the simple average of the two ends, which is 45 and 45 here. If your LMTD falls outside that range, one of your temperatures is probably in the wrong place.
Finally, remember that LMTD applies to the whole exchanger only if the assumptions hold. For quick estimates it is usually accurate enough, and for final design the result should be checked with a detailed rating program.
If you only need a rough comparison of two layouts, compare their LMTD values at the same duty. The higher one needs less area, all else being equal.
Frequently asked questions
What does LMTD stand for?
Log mean temperature difference, the average driving temperature difference across a heat exchanger.
Why is counter-flow better than parallel flow?
It keeps a larger temperature difference along the exchanger, so the same duty needs less area.
What is the correction factor F?
A factor below 1 that adjusts the counter-flow LMTD for exchangers with multiple passes or cross flow.
What if the two end differences are equal?
The formula becomes 0 divided by 0, and the LMTD equals that common difference.
Can I mix Celsius and Kelvin?
Yes, because only differences are used. A difference of 1 degree Celsius equals 1 kelvin. Just do not mix Fahrenheit with the others.