Refrigeration Line Sizing Calculator: Liquid & Suction Line Diameter

A refrigerant line has to carry the flow at a speed that keeps oil moving without wasting pressure. Enter the flow and a target velocity, and this calculator returns the minimum inside diameter for a liquid line or a suction line.

Lines & Line Sizing Calculators

Refrigeration Line Sizing Calculator

Minimum refrigerant line diameter for a liquid or suction/vapor line, from volumetric flow and a target line velocity.

GPM
ft/s
Enter the target liquid-line velocity from your system/refrigerant design guidance — recommended velocities vary by refrigerant and application.
This sizes a line from its volumetric flow and a velocity you specify — it does not look up refrigerant-specific pressure-drop or oil-return charts. For an actual installation, size lines using the manufacturer's or ASHRAE line-sizing tables for your specific refrigerant, capacity, and line length.

Starting values: the liquid mode opens with 3 GPM and a target velocity of 3 ft/s, giving 0.639 in. The suction mode opens with 15 CFM and 3,000 ft/min, giving 0.957 in. The velocities are examples, so use your system’s own design figures.

The formulas

Diameter = √(4 × Flow ÷ (π × Velocity))

The calculator converts the flow to cubic feet per second in liquid mode and uses cubic feet per minute against a velocity in feet per minute in suction mode, then converts the answer to inches.

Where:

  • Liquid flow = the volumetric flow in GPM, with 1 GPM = 0.002228 ft³/s
  • Vapour flow = the volumetric flow in CFM
  • Velocity = the target in ft/s for liquid and ft/min for vapour

Worked examples

Example 1: the default liquid line

3 GPM = 0.006684 ft³/s. Diameter = √(4 × 0.006684 ÷ (3.1416 × 3)) = √0.002837 = 0.0533 ft, which is 0.639 in.

Example 2: a faster liquid line

At 5 ft/s the same flow needs √(0.026736 ÷ 15.708) = 0.0413 ft, or 0.495 in. A higher velocity allows a smaller line.

Example 3: the default suction line

15 ÷ 3,000 = 0.005 ft². Diameter = √(4 × 0.005 ÷ 3.1416) = 0.0798 ft, or 0.957 in.

Example 4: slower vapour

At 1,000 ft/min, 15 CFM needs 0.015 ft², giving 0.1382 ft, or 1.658 in. At 4,000 ft/min it needs 0.829 in. Velocity has a large effect on the line size.

What velocities do designers aim for?

A trade-journal article on refrigeration piping, dated April 2000, gives these target velocities. It advises confirming the values against current industry standards.

Line Velocity target
Suction 700 to 4,000 ft/min
Discharge 500 to 3,500 ft/min
Liquid 125 to 450 ft/min
Condenser-to-receiver liquid 100 ft/min or less
Receiver-to-evaporator liquid under 300 ft/min

The liquid velocity in the calculator is entered in ft/s, so convert: 125 to 450 ft/min is about 2.1 to 7.5 ft/s. The default of 3 ft/s is 180 ft/min and sits inside the range.

Oil return and pressure drop

Oil and refrigerant vapour do not mix readily, so vapour velocity has to be high enough to carry oil back to the compressor. That is why a suction line has a minimum velocity as well as a maximum. The same article gives a pressure-drop target of 2°F or less of change in saturation temperature for each suction, discharge or liquid segment, and 1°F or less for HFC liquid lines.

Using the result

  • Choose the velocity from your refrigerant and system guidance.
  • The answer is a minimum inside diameter. Tubing is usually sold by outside diameter, so find the next standard size that gives at least that inside diameter.
  • Convert the mass flow of refrigerant to a volumetric flow first, since the calculator takes volume per time.
  • Check the line length and fittings against the maker’s tables.

What the calculator does not do

  • It does not look up refrigerant-specific pressure-drop or oil-return charts. The note says to size real lines using the maker’s or ASHRAE tables.
  • It does not convert mass flow or capacity into volume.
  • It mixes units by design, with liquid in GPM and ft/s and vapour in CFM and ft/min, so read the labels.
  • It does not account for line length, risers, bends or temperature.

For the flow speed in a water pipe, see the pipe line velocity calculator.

Velocity and size for a fixed flow

The table below uses the suction-line formula with the default 15 CFM to show how strongly velocity drives the minimum inside diameter. The diameter falls as the square root of the velocity rises.

Velocity (ft/min) Area (sq ft) Minimum inside diameter
700 0.0214 1.98 in
2,000 0.0075 1.17 in
3,000 0.0050 0.96 in
3,500 0.0043 0.89 in

Example 5: converting units

3,000 ft/min is 3,000 ÷ 60 = 50 ft/s, and 3 ft/s is 180 ft/min. 1 GPM is about 0.1337 cubic feet per minute, so the default 3 GPM is about 0.40 CFM. Convert first if your data comes in different units from the fields.

Why the same tube is not right for every load

A line sized for full load carries a lower velocity at part load, and a suction riser that is too large at low load may not carry oil back. For that reason designers look at both the maximum and the minimum velocity across the operating range. The calculator shows one design point, so run it for the smallest load you expect as well as the largest.

A simple check

Run the calculator at the minimum velocity from your guidance, then at the maximum, and compare both diameters with the tube size you plan to use. If the tube’s inside diameter falls between the two answers, it is at least in range at that flow.

Frequently asked questions

How do I size a refrigerant line?

Divide the volumetric flow by the target velocity to get the area, then find the diameter. For 15 CFM at 3,000 ft/min, the minimum inside diameter is about 0.96 in.

What velocity should I use?

One trade article gives 700 to 4,000 ft/min for suction lines, 500 to 3,500 for discharge and 125 to 450 for liquid lines. Confirm against current standards.

Why does suction velocity have a minimum?

Oil and vapour do not mix readily, so the vapour has to move fast enough to carry oil back to the compressor.

Is the result an inside or outside diameter?

Inside. Tubing is normally sold by outside diameter, so choose a standard size with at least that inside diameter.